Troubleshooting

To isolate a malfunction, proceed as follows:

  • Clearly define the problem (or symptom) and when it occurs.

  • Locate the problem in the Troubleshooting table.

  • Review all possible causes. Then, one-at-a-time, work through the list of corrections until the problem is solved.

Problem Cause Solution
Product not holding temperature

 

 

 

 

   

Control temperature set too low

Increase air temperature

Heat settings too low Remove front cover and adjust shelf and base heat settings

Heat settings too low

Have heat zones set to factory default temperatures

Door gasket damaged or worn

Replace bad door gaskets

Bad air heater

Check heaters and replace if bad See Tech Mode items 10 and 16

Bad air heater Check heaters and replace if bad
Blower not working Check blower and replace if bad
Blower not working Check blower and replace if bad See Tech Mode item 18

Bad air heater, or blower relays

Replace relay See Tech Mode items 10 and 16

Bad high limit Check high limit and replace if bad

Low or improper voltage

Compare receptacle voltage to data plate voltage

Air probe faulty, open (“E-6A”), or shorted (“E-6B”) Check probe resistance and replace, if necessary

Doors/drawers left open

Keep doors/drawers closed except to load and serve product

Product held too long

Hold product only for recommended times

Product not placed correctly in unit Place product in unit as per operation instructions.

Control temperature set too low

Increase air temperature (CDT control only)

or

Increase thermostat setting by removing hole plug on control panel and turning the shaft clockwise with a screwdriver

Product not hot when placed in unit

Place prepackaged hot food in unit

Cabinet steaming product soggy Humidity setpoint too high Decrease humidity setpoint
Water heater probe faulty, open (“E-12A”), or closed (“E-12B”) Check probe resistance and replace, if necessary

Bad humidity sensor (“E-17”)

Replace humidity sensor

Relay stuck closed Replace relay

Vent stuck closed (“E-80”)

  • Bad vent motor - replace

  • Check alignment and condition of mechanical vent parts

  • Vent acorn nuts too tight, loosen, if necessary

  Vent not set properly (units with vent adjustment only) Adjust vent
Product dry

 

Humidity set too low

Increase humidity setpoint

No water in pan

  • Check water shut-off valve

  • Adjust flow control valve

  • Check solenoid valve and relay

Bad float switch Replace float switch

Bad water heater high limit

Replace high limit

Bad water heater Check heater and replace if bad; see Tech Mode item 18

Vent stuck open ("E-80")

  • Bad vent motor - replace

  • Check alignment and condition of mechanical vent parts

Unit not reaching set temperature

 

 

Doors left open

Keep doors closed except to load and serve product

Door gasket damaged or worn

Replace bad door gaskets

Thermometer not indicating true temperature Check cabinet temperature with another thermometer; have thermometer replaced if necessary
Blower not working Check Blower and replace if bad
Blower not working Check Blower and replace if bad; see Tech Mode item 18

Bad air heater

Check heaters and replace if bad; see Tech Mode item 18

Bad air heater, or blower relays Replace relay
Defective high limit on one of heaters Check high limit; replace

Unit not heating

 

 

 

 

Bad high limit

Check high limit; replace if bad

Bad control board

Replace control board

Bad air heater or blower relays

Replace relay

Bad air heater

Check heaters and replace if bad; see Tech Mode item 18

Bad air heater Check heaters and replace if bad

Faulty wiring

Check for loose connections or broken wires

Blown fuse Change 15 amp fuse.
Faulty thermostat Check thermostat
Unit not heating

Bad control board

Check set point reading; if unit for heat below setpoint and not calling for heat, control board defective. Replace control board

Blower not working

Check blower and replace if bad; see Tech Mode item 18

Faulty contactor Check contactor and replace if necessary
Relay stuck closed Replace relay
Unit not heating

 

Bad air heater Check heaters and replace if bad

Faulty wiring

Check for loose connections or broken wires

Faulty solid-state relay (CDT units only) Replace solid-state relay
Faulty control board (CDT units only) Replace control board

Faulty thermostat

Check thermostat and replace if needed

Unit not heating Control board not calling for heat Verify set-point reading; if zone (see Zone Positions at left) tempeature is below setpoint and not calling for heat (no 5 vdc), control board defective

Water does not drain

Drain clogged

Remove drain obstruction

With switch in ON position the cabinet is completely inoperative Unit not connected to electrical supply Plug cord into electrical outlet
Open breaker or fuse Reset breaker or install new fuse in junction box

Faulty cord or plug

Check cord and plug

Faulty power switch Check power switch
In-unit resettable breakers

Press on each white resettable breaker button.

With power switch in POWER position, unit is completely inoperative (no power)

 

Open circuit

Check to see that unit is plugged in.

Check breaker or fuse at supply box.

Check control panel fuses per Replacing the Fuse and Fuse Holder.

Check voltage at wall receptacle.

Check POWER switch; replace if defective.

Check cord and plug for loose connections.

Control board defective

Check for 12 volt input from transformer; replace if defective

Transformer defective Check input and output voltage; replace if defective
Shelf won't heat

 

Shelf not plugged into receptacle properly Check that the shelf plug is firmly pushed into receptacle in the interior of the unit.
Faulty shelf heat relay Check and replace if necessary
Faulty shelf heater Check and replace if necessary

Unit not preheated

Preheat unit before loading product

Faulty PC board Replace PC board
Temperature setting “OFF” Remove front cover and increase shelf heat setting
Unit overheating

 

Faulty thermostat Check thermostat; replace thermostat

Faulty blower

Check blowers; replace blower

Faulty control board (CDT units only) Replace control board.
 

Faulty blowers

Check blowers; replace blower

No base heat

 

Faulty base heat relay Check and replace if necessary

Faulty base heater

Check and replace if necessary

Unit not preheated Preheat unit before loading product
Faulty PC board Replace PC board
No light(s)

 

Faulty contactor Check contactor and replace if necessary
Light socket shorted Replace light socket

Faulty fluorescent light bulb

Replace fluourescent light bulb

Faulty lamp ballast Replace ballast
With power switch turned on, the blower and fan operate, but the power light is off and the unit won’t heat Open high limit

With unit cool, check high limit

If the high limit opened because of overheating, refer to Unit Overheats section of Troubleshooting Guide

Red LED, when should be green, or vice versa Polarity reversed on LED wires Access the LED wires on side of unit and reverse wires at wire nuts
Front LED does not light Faulty LED Access LED wires on side of unit and check for dc voltage; if no voltage, check for voltage at control board; if voltage present, replace LED
Individual zone does not heat

 

Faulty heat relay

Testing for proper relay operation:

To avoid electrical shock, make connections before applying power, take reading, and remove power before removing meter leads. The following checks are performed with the wall circuit breaker closed and the main power switch in the ON position.

  1. With no power (5 vdc) going to the relay, 120 volts should show on the output side of the relay, and 0 volts on the input (5 volts). If no 120 volts, check for open heater, and if heater is OK, replace relay.

  2. With the component energized, 0 volts should show on the output side of the relay, and 5 vdc on the input side. If not, replace relay. Also, check for reverse polarity of 5 vdc to relay-reference wiring diagram.

  3. If voltage varies from steps 1 and 2, remove power to unit pull input wires from relay and place leads of meter onto input wires. Reapply power to unit. When unit is running, if the input wires to relay shows 5vdc, the relay is faulty.

Faulty heater

Refer to wiring diagrams and with the outputs on, check across terminal #1 of the appropriate relay and the neutral wire (#N5 on 554 or #N2 on 1L or 22) at the transformer. If meter shows full voltage (120V), but heater is not heating, replace heater and liner assy.

Refer to wiring diagrams and disconnect 15-pin connector at control board. With an ohm meter, check between the appropriate terminals on connector and the corresponding terminal on the terminal block. Meter should read 35 to 41 ohms at room temperature. Replace liner and heater assy if necessary

Faulty heater RTD Refer to wiring diagram and disconnect 15-pin connector at control board. With an ohm meter, check between the appropriate terminals on connector, based upon which RTD is being checked. Meter should read about 1080 ohms at room temperature. Replace liner and heater assy. if necessary.