CFE 410/420 Troubleshooting an E-29 Error Code
multimeter
Overview
-
Amp draw detected on the amp sensor input when there is no call for heat (heat light off) most likely caused by a sticking contactor.
-
Control activates the shunt trip circuit with 24VAC on wires SH1 and SH2.
-
Breaker trips and will require a manual reset.
-
E-29 error code appears on display.
Troubleshooting a Tripped Breaker
Narrow down the cause of the tripped breaker:
-
The breaker tripped because the amp draw exceeded the rating for the breaker.
-
The breaker is defective or worn out tripping >10% below its amp rating.
-
The breaker tripped due to activation of the shunt (amp draw detected when not calling for heat).
-
Reset breaker
-
Enter tech mode by pressing and holding the Program button for 6 seconds.
-
Enter code 11221122.
-
Use the filter buttons to navigate to step T-24.
-
Toggle this step from NO to YES with the right timer button
-
Turn on fryer.
-
Check the error log for recent errors.
-
If there are E-25 HEAT AMPS TOO HIGH errors, then enter INFO MODE and navigate to 20. AMPS to check what the control reads for amp draw before the breaker trips.
-
Verify this reading with an amp clamp by taking amp draw next to the amp sensor rings.
-
If this amp rating exceeds the amp rating of the breaker, find the wiring short and correct.
-
If the amp draw reading in step 20. AMPS is false, complete step 7.
-
-
If the breaker does not trip, do both of the following:
-
Check the ohm value on all three amp sensors. They should all read the same value. If they do not, replace the amp sensors.
-
Check the voltage on the control. It should have a constant 24V AC output on SH1 and SH2. If it does not, reinitialize the control. If there is no change, replace the control.
-
-
If this still trips the breaker immediately, then check amp draw with an amp clamp next to the amp sensor rings.
-
If the amp draw exceeds the rating of the breaker, find the wiring issue and correct.
-
If the amp draw is >10% lower than the rating of the breaker and the breaker trips, replace the breaker.
-
Testing
-
To test this output, you must enter MFG mode and press 1 for the control test.
-
Then navigate to step CT-14 Outputs and the display will say F_I_S_H and buttons 1 - 4 are illuminated.
-
Press button 4 and this will trip the shut breaker and there will be an asterisk next to "H".
-
If it doesn't trip, check for 24V when energized at wires SH1 and SH2. and that the wires are connected to the shunt portion of the breaker.
-
If voltage exists at wires SH1 and SH2 at the breaker and the breaker doesn't trip, replace the breaker.
Related Content
Replacing the High Limit Module
CFE 410/420 Troubleshooting the Solid State High Limit
Temperature Probe Gauge Instructions
CFE 410/420 Troubleshooting the E-5 Oil Overheating Error Code
CFE 410/420 Troubleshooting the E-6 Temperature Probe Error Code
CFE 410/420 Troubleshooting the E-10 High Limit Error Code
CFE 410/420 Troubleshooting the E-20A Fan Sensor Stuck On Error Code
CFE 410/420 Troubleshooting the E-26 Heat Amps Locked On Error Code
CFE 410/420 Troubleshooting the E-27 Amps Too Low Error Code
CFE 410/420 Troubleshooting the Voltage Conversion
CFE 410/420 Troubleshooting the W-1 Low Voltage Error Code
CFE 410/420 Troubleshooting the W-2 Slow Heating Error Code
CFE 410/420 Troubleshooting the W-3 Was Not Ready Error Code
CFE 410/420 Troubleshooting the W-4 Slow Cooking Error Code
CFE 410/420 Troubleshooting the W-5 Slow Cooking Error Code
CFE 410/420 Troubleshooting the W-6 Slow Cooking Error Code
CFE 410/420 Troubleshooting the W-7 Low Amps Error Code
CFE 410/420 Troubleshooting the W-9 Discard Product Error Code
CFE 410/420 Troubleshooting the E-92 24V Current Limiter Fuse Tripped Error Code
Reference